With integrated under voltage releaseNo
Type of electrical connection of main circuitScrew connection
With thermal protectionYes
Degree of protection (IP)IP20
Rated operating voltage400 - 400V
Type of control elementRocker lever
With integrated auxiliary switchNo
Switch off techniqueMagnetic
Rated operation power at AC-3, 230 V0kW
Device constructionComplete device in housing
Phase failure sensitiveNo
Adjustment range undelayed short-circuit release250 - 325A
Rated operation power at AC-3, 400 V11kW
Rated permanent current Iu20A
Overload release current setting16 - 25A
Rated short-circuit breaking capacity lcu at 400 V, AC10kA