Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Type of electrical connection of main circuit
Screw connection
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
0 - 0A
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
125 - 160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
25kA
Rated voltage
440 - 440V
Adjustment range undelayed short-circuit release
960 - 1600A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of control element
Rocker lever
Number of poles
3
Integrated earth fault protection
No
With switched-off indicator
No
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Related products
From same serie
NZMB2-A160

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Type of electrical connection of main circuit
Screw connection
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
0 .. 0A
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
125 .. 160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
25kA
Rated voltage
440 .. 440V
Adjustment range undelayed short-circuit release
960 .. 1600A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of control element
Rocker lever
Number of poles
3
Integrated earth fault protection
With switched-off indicator
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Motor drive integrated
Motor drive optional
From same serie