Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated voltage
690 - 690V
Overload release current setting
125 - 160A
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
0 - 0A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
960 - 1600A
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
Yes
Number of poles
3
Type of control element
Rocker lever
With integrated under voltage release
No
Motor drive integrated
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Related products
From same serie
NZMH2-A160

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated voltage
690 .. 690V
Overload release current setting
125 .. 160A
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
0 .. 0A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
960 .. 1600A
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of poles
3
Type of control element
Rocker lever
With integrated under voltage release
Motor drive integrated
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
From same serie
Related products
We use cookies to enhance your experience.