Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Adjustment range undelayed short-circuit release1200 - 1200A
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally open contact0
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Position of connection for main current circuitFront side
With integrated under voltage releaseNo
Motor drive integratedNo
Type of electrical connection of main circuitScrew connection
Overload release current setting50 - 100A
DIN rail (top hat rail) mounting optionalYes
Motor drive optionalYes
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Type of control elementRocker lever
With switched-off indicatorNo
Rated voltage690 - 690V
Complete device with protection unitYes
Number of poles3
Rated permanent current Iu100A
Adjustment range short-term delayed short-circuit release100 - 1000A
Degree of protection (IP)IP20

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH2-VE100

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Adjustment range undelayed short-circuit release

1200 .. 1200A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally open contact

0

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Position of connection for main current circuit

Front side

With integrated under voltage release

Motor drive integrated

Type of electrical connection of main circuit

Screw connection

Overload release current setting

50 .. 100A

DIN rail (top hat rail) mounting optional

Motor drive optional

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally closed contact

0

Type of control element

Rocker lever

With switched-off indicator

Rated voltage

690 .. 690V

Complete device with protection unit

Number of poles

3

Rated permanent current Iu

100A

Adjustment range short-term delayed short-circuit release

100 .. 1000A

Degree of protection (IP)

IP20

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.