Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
Technical specifications
With integrated under voltage release
No
Type of electrical connection of main circuit
Other
Rated permanent current Iu
40A
With integrated auxiliary switch
No
Type of control element
Rocker lever
Height
145mm
Depth
88mm
Switch off technique
Thermomagnetic
Width
90mm
Rated short-circuit breaking capacity lcu at 400 V, AC
35kA
Rated operation power at AC-3, 400 V
18.5kW
Rated operating voltage
690 - 690V
Phase failure sensitive
Yes
Overload release current setting
32 - 40A
With thermal protection
Yes
Adjustment range undelayed short-circuit release
320 - 560A
Rated operation power at AC-3, 230 V
11kW
Number of poles
3
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Related products
From same serie
NZMN1-M40

Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
Technical specifications
With integrated under voltage release
Type of electrical connection of main circuit
Other
Rated permanent current Iu
40A
With integrated auxiliary switch
Type of control element
Rocker lever
Height
145mm
Depth
88mm
Switch off technique
Thermomagnetic
Width
90mm
Rated short-circuit breaking capacity lcu at 400 V, AC
35kA
Rated operation power at AC-3, 400 V
18.5kW
Rated operating voltage
690 .. 690V
Phase failure sensitive
Overload release current setting
32 .. 40A
With thermal protection
Adjustment range undelayed short-circuit release
320 .. 560A
Rated operation power at AC-3, 230 V
11kW
Number of poles
3
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
From same serie