Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz37kA
Rated voltage690 - 690V
DIN rail (top hat rail) mounting optionalNo
Number of poles4
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release1250 - 12500A
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitFront side
With integrated under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitScrew connection
Number of auxiliary contacts as normally closed contact0
Overload release current setting630 - 1250A
Number of auxiliary contacts as change-over contact0
Integrated earth fault protectionNo
Motor drive optionalYes
Complete device with protection unitYes
Adjustment range undelayed short-circuit release2500 - 15000A
Motor drive integratedNo
Degree of protection (IP)IP20
Type of control elementRocker lever
With switched-off indicatorNo
Rated permanent current Iu800A

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMN4-4-VE1250/800

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

37kA

Rated voltage

690 .. 690V

DIN rail (top hat rail) mounting optional

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

1250 .. 12500A

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Front side

With integrated under voltage release

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Screw connection

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

630 .. 1250A

Number of auxiliary contacts as change-over contact

0

Integrated earth fault protection

Motor drive optional

Complete device with protection unit

Adjustment range undelayed short-circuit release

2500 .. 15000A

Motor drive integrated

Degree of protection (IP)

IP20

Type of control element

Rocker lever

With switched-off indicator

Rated permanent current Iu

800A

Related products