Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
1000A
Integrated earth fault protection
No
With integrated under voltage release
No
Rated voltage
690 - 690V
Type of control element
Rocker lever
With switched-off indicator
No
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
2000 - 12000A
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Overload release current setting
500 - 1000A
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
No
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Position of connection for main current circuit
Front side
Related products
From same serie
NZMH4-4-VE1000

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1000A
Integrated earth fault protection
With integrated under voltage release
Rated voltage
690 .. 690V
Type of control element
Rocker lever
With switched-off indicator
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
2000 .. 12000A
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Overload release current setting
500 .. 1000A
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Position of connection for main current circuit
Front side
From same serie
Related products
We use cookies to enhance your experience.