ManufacturerEaton
Catalog number278483
TypePKZM01-6,3
CategoryMotor protection circuit-breaker
EAN code4015082784836
Details
- •Low-voltage industrial components
- •Motor protection circuit-breaker
- •1 KOM
- •EATON
Technical specifications
Depth93mm
Width45mm
With integrated auxiliary switchNo
Height90mm
Rated operating voltage690 - 690V
With integrated under voltage releaseNo
With thermal protectionNo
Degree of protection (IP)IP20
Type of control elementPush button
Power loss5.68W
Switch off techniqueThermomagnetic
Type of electrical connection of main circuitScrew connection
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release98 - 98A
Phase failure sensitiveYes
Rated operation power at AC-3, 230 V1.1kW
Rated operation power at AC-3, 400 V2.2kW
Rated permanent current Iu6.3A
Number of poles3
Overload release current setting4 - 6.3A
Rated short-circuit breaking capacity lcu at 400 V, AC50kA
Related products
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user
PKZM01-6,3

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
DetailsTechnical specificationsRelated products
Technical specifications
Depth
93mm
Width
45mm
With integrated auxiliary switch
Height
90mm
Rated operating voltage
690 .. 690V
With integrated under voltage release
With thermal protection
Degree of protection (IP)
IP20
Type of control element
Push button
Power loss
5.68W
Switch off technique
Thermomagnetic
Type of electrical connection of main circuit
Screw connection
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
98 .. 98A
Phase failure sensitive
Rated operation power at AC-3, 230 V
1.1kW
Rated operation power at AC-3, 400 V
2.2kW
Rated permanent current Iu
6.3A
Number of poles
3
Overload release current setting
4 .. 6.3A
Rated short-circuit breaking capacity lcu at 400 V, AC
50kA
Related products
VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.