Technical specifications

Built-in depth70.5mm
Rated insulation voltage Ui440V
Release characteristicC
Frequency50 - 60Hz
Voltage typeAC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Over voltage category3
Degree of protection (IP)IP20
Concurrently switching neutral conductorYes
Rated voltage230V
Rated current32A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Number of protected poles1
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA
Power loss5.4W
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
Rated impulse withstand voltage Uimp4kV
Width in number of modular spacings1
Number of poles (total)2
Flush-mounted installationNo
Current limiting class3
Additional equipment possibleYes
Pollution degree2
Ambient temperature during operating-25 - 75°C
Explosion-proofNo
Connectable conductor cross section multi-wired1 - 25mm²
Connectable conductor cross section solid-core1 - 25mm²
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

FAZ-PN-C32/1N

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • EATON

Technical specifications

Built-in depth

70.5mm

Rated insulation voltage Ui

440V

Release characteristic

C

Frequency

50 .. 60Hz

Voltage type

AC

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Over voltage category

3

Degree of protection (IP)

IP20

Concurrently switching neutral conductor

Rated voltage

230V

Rated current

32A

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Number of protected poles

1

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Power loss

5.4W

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA

Rated impulse withstand voltage Uimp

4kV

Width in number of modular spacings

1

Number of poles (total)

2

Flush-mounted installation

Current limiting class

3

Additional equipment possible

Pollution degree

2

Ambient temperature during operating

-25 .. 75°C

Explosion-proof

Connectable conductor cross section multi-wired

1 .. 25mm²

Connectable conductor cross section solid-core

1 .. 25mm²