Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu1250A
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact0
Adjustment range short-term delayed short-circuit release1250 - 12500A
Adjustment range undelayed short-circuit release2500 - 15000A
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
With switched-off indicatorNo
Position of connection for main current circuitFront side
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitScrew connection
Type of control elementRocker lever
Overload release current setting630 - 1250A
Motor drive integratedNo
Complete device with protection unitYes
Number of auxiliary contacts as normally closed contact0
Motor drive optionalYes
Degree of protection (IP)IP20
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Rated voltage1000 - 1000V
Number of poles3

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH4-VE1250-S1

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

1250A

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as change-over contact

0

Adjustment range short-term delayed short-circuit release

1250 .. 12500A

Adjustment range undelayed short-circuit release

2500 .. 15000A

With integrated under voltage release

Device construction

Built-in device fixed built-in technique

With switched-off indicator

Position of connection for main current circuit

Front side

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Screw connection

Type of control element

Rocker lever

Overload release current setting

630 .. 1250A

Motor drive integrated

Complete device with protection unit

Number of auxiliary contacts as normally closed contact

0

Motor drive optional

Degree of protection (IP)

IP20

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Rated voltage

1000 .. 1000V

Number of poles

3