Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu300A
Adjustment range short-term delayed short-circuit release0 - 0A
Rated voltage690 - 690V
Adjustment range undelayed short-circuit release2000 - 2500A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Overload release current setting240 - 300A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of poles3
Complete device with protection unitYes
Number of auxiliary contacts as change-over contact0
Motor drive integratedNo
With switched-off indicatorNo
Type of control elementRocker lever
With integrated under voltage releaseNo
Type of electrical connection of main circuitFrame clamp
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Motor drive optionalYes

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH2-A300-BT

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

300A

Adjustment range short-term delayed short-circuit release

0 .. 0A

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

2000 .. 2500A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Overload release current setting

240 .. 300A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of poles

3

Complete device with protection unit

Number of auxiliary contacts as change-over contact

0

Motor drive integrated

With switched-off indicator

Type of control element

Rocker lever

With integrated under voltage release

Type of electrical connection of main circuit

Frame clamp

Device construction

Built-in device fixed built-in technique

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Motor drive optional

Related products