Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release480 - 800A
With switched-off indicatorNo
Type of control elementRocker lever
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitFrame clamp
Overload release current setting63 - 80A
Adjustment range short-term delayed short-circuit release0 - 0A
Number of auxiliary contacts as change-over contact0
Integrated earth fault protectionNo
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalYes
Motor drive integratedNo
Position of connection for main current circuitFront side
Motor drive optionalYes
Rated permanent current Iu80A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA