Technical specifications

Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release0 - 0A
With switched-off indicatorNo
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
Integrated earth fault protectionNo
Rated permanent current Iu250A
Type of electrical connection of main circuitScrew connection
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Motor drive optionalYes
Number of auxiliary contacts as normally open contact0
Adjustment range undelayed short-circuit release500 - 2750A
Degree of protection (IP)IP20
Rated voltage690 - 690V
Number of poles3
Position of connection for main current circuitFront side
Overload release current setting125 - 250A
Type of control elementRocker lever
Motor drive integratedNo

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH3-AE250-AVE

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

0 .. 0A

With switched-off indicator

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Integrated earth fault protection

Rated permanent current Iu

250A

Type of electrical connection of main circuit

Screw connection

Suitable for DIN rail (top hat rail) mounting

With integrated under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Motor drive optional

Number of auxiliary contacts as normally open contact

0

Adjustment range undelayed short-circuit release

500 .. 2750A

Degree of protection (IP)

IP20

Rated voltage

690 .. 690V

Number of poles

3

Position of connection for main current circuit

Front side

Overload release current setting

125 .. 250A

Type of control element

Rocker lever

Motor drive integrated