Details
- •odvodnik prenapona V10, 3+1, 280V,
- •Earthing, lightning and surge protection
- •Surge protection device for power supply systems
- •1 KOM
- •OBO
Technical specifications
With remote signalling contactNo
Nominal voltage DC-V
Number of conductors (without earthing)-
Integrated short-circuit protectionNo
Integrated backup fuseNo
Max. overcurrent protection device, series connection (fuse)-A
Max. PV-voltage-V
Leakage-current freeNo
System configuration otherNo
Max. overcurrent protection device, parallel connection (fuse)-A
Short-circuit breaking capacity (Isccr)-kA
Max. conductor cross section flexible (fine-strand)-mm²
System configuration TN-CNo
Max. continuous voltage DC-V
Voltage protection level N-PE-kV
Voltage protection level L-N-kV
System configuration DCNo
System configuration ITNo
Integrated short-circuit protection selective to fuse gG-A
System configuration TNYes
System configuration TTYes
Voltage protection level1.1kV
Mounting methodDIN rail (top hat rail) 35 mm
System configuration TN-SYes
Max. discharge surge current (8/20)20kA
Category type 2Yes
Max. continuous voltage AC280V
Signalling at the deviceOptic
System configuration TN-C-SYes
Max. conductor cross section solid (solid, stranded)35mm²
Construction size4 modular spacing
Nominal discharge surge current (8/20)10kA
Nominal voltage AC230V
Degree of protection (IP)IP20