Details
- •Low-voltage industrial components
- •Motor starter/motor starter combination
- •1 KOM
- •EATON
Technical specifications
MSC-DEA-4-M7(24VDC)

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Motor starter/motor starter combination
- 1 KOM
- EATON
Technical specifications
Supporting protocol for DeviceNet
Number of auxiliary contacts as normally closed contact
1
Supporting protocol for INTERBUS
Supporting protocol for Data-Highway
Supporting protocol for LON
Supporting protocol for TCP/IP
Rated operation current Ie
3.6A
Supporting protocol for CAN
Rated operation power at AC-3, 400 V
1.5kW
Number of command positions
0
Depth
102mm
Supporting protocol for PROFIBUS
Supporting protocol for Modbus
With transformer
Width
45mm
Number of indicator lights
0
Height
198mm
Overload release current setting
1 .. 4A
Supporting protocol for ASI
Number of auxiliary contacts as normally open contact
0
Suitable for emergency stop
Supporting protocol for SUCONET
External reset possible
Supporting protocol for other bus systems
Rail mounting possible
With short-circuit release
Rated control supply voltage Us at DC
24 .. 24V
Supporting protocol for AS-Interface Safety at Work
Type of motor starter
Direct online starter (DOL)
Voltage type for actuating
DC
Rated control supply voltage Us at AC 60HZ
0 .. 0V
Supporting protocol for EtherNet/IP
Supporting protocol for DeviceNet Safety
Supporting protocol for PROFINET IO
Supporting protocol for PROFIsafe
With fuse
Supporting protocol for SafetyBUS p
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP)
IP20
Release class
Adjustable
Type of electrical connection for auxiliary- and control current circuit
Screw connection
Supporting protocol for SERCOS
Supporting protocol for PROFINET CBA
Rated control supply voltage Us at AC 50HZ
0 .. 0V
Supporting protocol for INTERBUS-Safety
Supporting protocol for Foundation Fieldbus
Rated operation power at AC-3, 230 V, 3-phase
0.75kW
Rated operation current at AC-3, 400 V
4A
Rated power, 575 V, 60 Hz, 3-phase
0kW
Rated power, 460 V, 60 Hz, 3-phase
0kW
Rated conditional short-circuit current, type 1, 480 Y/277 V
0A
Degree of protection (NEMA)
Other
Ambient temperature, upper operating limit
55°C
Coordination class according to IEC 60947-4-3
Class 1
Rated conditional short-circuit current, type 2, 400 V
100A
Rated conditional short-circuit current, type 2, 230 V
0A
Temperature compensated overload protection
Rated conditional short-circuit current, type 1, 600 Y/347 V
0A