- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
250A
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Overload release current setting
125 - 250A
Device construction
Built-in device plug-in technique
DIN rail (top hat rail) mounting optional
Yes
Type of electrical connection of main circuit
Screw connection
Adjustment range short-term delayed short-circuit release
250 - 2500A
Adjustment range undelayed short-circuit release
3000 - 3000A
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Number of poles
4
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
With switched-off indicator
No
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
No
Motor drive integrated
No
Related products
From same serie
NZMH2-4-VE250/160-SVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
250A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Overload release current setting
125 .. 250A
Device construction
Built-in device plug-in technique
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Adjustment range short-term delayed short-circuit release
250 .. 2500A
Adjustment range undelayed short-circuit release
3000 .. 3000A
Motor drive optional
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Number of poles
4
Degree of protection (IP)
IP20
Complete device with protection unit
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Motor drive integrated