Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- ABB
Technical specifications
Rated operation power at AC-3, 230 V
-kW
Phase failure sensitive
Yes
Rated operating voltage
690 - 690V
Overload release current setting
16 - 20A
Device construction
Complete device in housing
Type of electrical connection of main circuit
Screw connection
With thermal protection
Yes
Rated operation power at AC-3, 400 V
7.5kW
Rated permanent current Iu
20A
Adjustment range undelayed short-circuit release
300 - 300A
With integrated auxiliary switch
No
Switch off technique
Thermomagnetic
Type of control element
Turn button
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, AC
16kA
Depth
85.4mm
Width
45mm
Height
97.8mm
Number of poles
3
Degree of protection (IP)
IP20
From same serie
1SAM250000R1013 | MS116-20

Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- ABB
Technical specifications
Rated operation power at AC-3, 230 V
-kW
Phase failure sensitive
Rated operating voltage
690 .. 690V
Overload release current setting
16 .. 20A
Device construction
Complete device in housing
Type of electrical connection of main circuit
Screw connection
With thermal protection
Rated operation power at AC-3, 400 V
7.5kW
Rated permanent current Iu
20A
Adjustment range undelayed short-circuit release
300 .. 300A
With integrated auxiliary switch
Switch off technique
Thermomagnetic
Type of control element
Turn button
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, AC
16kA
Depth
85.4mm
Width
45mm
Height
97.8mm
Number of poles
3
Degree of protection (IP)
IP20
From same serie