Type of electrical connection of main circuitBolt connection
Rated voltage690 - 690V
Device constructionBuilt-in device fixed built-in technique
Type of control elementToggle
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release150.0 - 2500A
Motor drive optionalYes
Degree of protection (IP)IP20
With switched-off indicatorNo
Rated permanent current Iu250A
Motor drive integratedNo
With under voltage releaseNo
Overload release current setting100.0 - 250A
Number of poles4
Adjustment range undelayed short-circuit release375.0 - 3000A
Complete device with protection unitYes
Position of connection for main current circuitFront side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA054065R1 | T4H 250 PR222DS/P-LSI IN=250 4P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuit

Bolt connection

Rated voltage

690 .. 690V

Device construction

Built-in device fixed built-in technique

Type of control element

Toggle

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Motor drive optional

Degree of protection (IP)

IP20

With switched-off indicator

Rated permanent current Iu

250A

Motor drive integrated

With under voltage release

Overload release current setting

100.0 .. 250A

Number of poles

4

Adjustment range undelayed short-circuit release

375.0 .. 3000A

Complete device with protection unit

Position of connection for main current circuit

Front side

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

DIN rail (top hat rail) mounting optional