Technical specifications

Rated voltage690 - 690V
Number of poles3
Rated permanent current Iu250A
Overload release current setting64.0 - 160A
Degree of protection (IP)IP20
Motor drive integratedNo
Type of control elementToggle
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitFront side
Adjustment range short-term delayed short-circuit release96.0 - 1600A
Adjustment range undelayed short-circuit release240.0 - 1920A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
With switched-off indicatorNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
With under voltage releaseNo
Complete device with protection unitYes
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA054079R1 | T4L 250 PR222DS/P-LSIG IN=160 3P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Number of poles

3

Rated permanent current Iu

250A

Overload release current setting

64.0 .. 160A

Degree of protection (IP)

IP20

Motor drive integrated

Type of control element

Toggle

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Front side

Adjustment range short-term delayed short-circuit release

96.0 .. 1600A

Adjustment range undelayed short-circuit release

240.0 .. 1920A

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

With switched-off indicator

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

With under voltage release

Complete device with protection unit

Motor drive optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.