Technical specifications

Rated permanent current Iu250A
Integrated earth fault protectionNo
Overload release current setting64.0 - 160A
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitFront side
Suitable for DIN rail (top hat rail) mountingNo
Number of poles4
With under voltage releaseNo
Degree of protection (IP)IP20
Adjustment range undelayed short-circuit release160 - 1600A
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Adjustment range short-term delayed short-circuit release160 - 1600A
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
With switched-off indicatorNo
Type of control elementToggle
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA054085R1 | T4L 250 PR221DS-I IN=160 4P F F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

250A

Integrated earth fault protection

Overload release current setting

64.0 .. 160A

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Front side

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

With under voltage release

Degree of protection (IP)

IP20

Adjustment range undelayed short-circuit release

160 .. 1600A

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Adjustment range short-term delayed short-circuit release

160 .. 1600A

Motor drive optional

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

With switched-off indicator

Type of control element

Toggle

Motor drive integrated