Technical specifications
1SDA054103R1 | T4V 250 PR222DS/P-LSIG IN=160 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
96.0 .. 1600A
Adjustment range undelayed short-circuit release
240.0 .. 1920A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Overload release current setting
64.0 .. 160A
Position of connection for main current circuit
Front side
Rated permanent current Iu
250A
Motor drive optional
Type of control element
Toggle
With switched-off indicator
Motor drive integrated
DIN rail (top hat rail) mounting optional
Number of poles
3
Device construction
Built-in device fixed built-in technique
With under voltage release
Integrated earth fault protection
Degree of protection (IP)
IP20
Complete device with protection unit
Rated voltage
690 .. 690V