Technical specifications

Rated permanent current Iu320A
Type of electrical connection of main circuitBolt connection
Type of control elementToggle
Motor drive integratedNo
Rated voltage690 - 690V
Number of poles4
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Overload release current setting128.0 - 320A
Adjustment range undelayed short-circuit release320 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release320 - 3200A
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
With switched-off indicatorNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA054121R1 | T4N 320 PR221DS-LS IN=320 4P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

320A

Type of electrical connection of main circuit

Bolt connection

Type of control element

Toggle

Motor drive integrated

Rated voltage

690 .. 690V

Number of poles

4

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Overload release current setting

128.0 .. 320A

Adjustment range undelayed short-circuit release

320 .. 3200A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

36kA

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

Adjustment range short-term delayed short-circuit release

320 .. 3200A

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

With under voltage release

DIN rail (top hat rail) mounting optional

Complete device with protection unit

With switched-off indicator