Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA054339R1 | T5S 400 PR222DS/P-LSIG IN=400 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
160.0 .. 400A
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
With under voltage release
Adjustment range undelayed short-circuit release
600.0 .. 4800A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Adjustment range short-term delayed short-circuit release
240.0 .. 4000A
Rated permanent current Iu
400A
Integrated earth fault protection
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of poles
3
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Type of control element
Rocker lever
Motor drive optional
Complete device with protection unit