Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu630A
Number of poles3
Overload release current setting252.0 - 630A
Motor drive integratedNo
Position of connection for main current circuitFront side
Type of control elementToggle
Degree of protection (IP)IP20
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Adjustment range short-term delayed short-circuit release378.0 - 6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Adjustment range undelayed short-circuit release945.0 - 5985A
With switched-off indicatorNo
Motor drive optionalYes
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA054414R1 | T5H 630 PR222DS/P-LSI IN=630 3P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

630A

Number of poles

3

Overload release current setting

252.0 .. 630A

Motor drive integrated

Position of connection for main current circuit

Front side

Type of control element

Toggle

Degree of protection (IP)

IP20

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Bolt connection

Adjustment range short-term delayed short-circuit release

378.0 .. 6300A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Adjustment range undelayed short-circuit release

945.0 .. 5985A

With switched-off indicator

Motor drive optional

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.