Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA059523R1 | T4L 250 PR223DS IN=160 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
Rated permanent current Iu
250A
Overload release current setting
64.0 .. 160A
Number of poles
3
Degree of protection (IP)
IP20
Type of control element
Toggle
With switched-off indicator
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
96.0 .. 1600A
Adjustment range undelayed short-circuit release
240.0 .. 1920A
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
With under voltage release