Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
No
Rated permanent current Iu
630A
Integrated earth fault protection
No
Overload release current setting
252.0 - 630A
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Motor drive integrated
No
Number of poles
4
Degree of protection (IP)
IP20
Motor drive optional
Yes
Type of control element
Toggle
Complete device with protection unit
Yes
Adjustment range undelayed short-circuit release
945.0 - 5985A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
From same serie
1SDA059534R1 | T5N 630 PR223DS IN=630 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
Rated permanent current Iu
630A
Integrated earth fault protection
Overload release current setting
252.0 .. 630A
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Motor drive integrated
Number of poles
4
Degree of protection (IP)
IP20
Motor drive optional
Type of control element
Toggle
Complete device with protection unit
Adjustment range undelayed short-circuit release
945.0 .. 5985A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique