Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
With switched-off indicator
No
Integrated earth fault protection
No
Position of connection for main current circuit
Front side
Adjustment range short-term delayed short-circuit release
240.0 - 4000A
Motor drive integrated
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Motor drive optional
Yes
Rated permanent current Iu
400A
Number of poles
3
Overload release current setting
160.0 - 400A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
600.0 - 4800A
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Number of auxiliary contacts as change-over contact
0
From same serie
1SDA059555R1 | T5V 400 PR223DS IN=400 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Integrated earth fault protection
Position of connection for main current circuit
Front side
Adjustment range short-term delayed short-circuit release
240.0 .. 4000A
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Motor drive optional
Rated permanent current Iu
400A
Number of poles
3
Overload release current setting
160.0 .. 400A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
600.0 .. 4800A
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Number of auxiliary contacts as change-over contact
0
From same serie