Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release- - -A
With integrated under voltage releaseNo
Rated permanent current Iu630A
Rated voltage690 - 690V
Overload release current setting441.0 - 630A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release3150 - 6300A
Type of electrical connection of main circuitBolt connection
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
Number of auxiliary contacts as change-over contact0
Complete device with protection unitYes
With switched-off indicatorNo
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitFront side
Type of control elementToggle
Degree of protection (IP)IP20
Motor drive optionalYes
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA060202R1 | T6N 630 TMA 630-6300 3P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

- .. -A

With integrated under voltage release

Rated permanent current Iu

630A

Rated voltage

690 .. 690V

Overload release current setting

441.0 .. 630A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

36kA

Integrated earth fault protection

Adjustment range undelayed short-circuit release

3150 .. 6300A

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

Number of auxiliary contacts as change-over contact

0

Complete device with protection unit

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Front side

Type of control element

Toggle

Degree of protection (IP)

IP20

Motor drive optional

Motor drive integrated