Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated permanent current Iu
800A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Integrated earth fault protection
No
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Degree of protection (IP)
IP20
Motor drive integrated
No
Type of electrical connection of main circuit
Bolt connection
Motor drive optional
Yes
Complete device with protection unit
Yes
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
4000 - 8000A
Type of control element
Toggle
Overload release current setting
560.0 - 800A
1SDA060214R1 | T6N 800 TMA 800-8000 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated permanent current Iu
800A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP20
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Motor drive optional
Complete device with protection unit
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
4000 .. 8000A
Type of control element
Toggle
Overload release current setting
560.0 .. 800A