Rated permanent current Iu800A
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Type of electrical connection of main circuitBolt connection
Rated voltage690 - 690V
Motor drive integratedNo
With switched-off indicatorNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Overload release current setting320.0 - 800A
Type of control elementToggle
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1200.0 - 9600A
Integrated earth fault protectionYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Motor drive optionalYes
Number of poles4
Adjustment range short-term delayed short-circuit release480.0 - 7600A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA060297R1 | T6H 800 PR222DS/P-LSIG IN=800 4P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

With integrated under voltage release

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP20

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Type of electrical connection of main circuit

Bolt connection

Rated voltage

690 .. 690V

Motor drive integrated

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Overload release current setting

320.0 .. 800A

Type of control element

Toggle

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1200.0 .. 9600A

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Motor drive optional

Number of poles

4

Adjustment range short-term delayed short-circuit release

480.0 .. 7600A