Technical specifications

Number of auxiliary contacts as change-over contact0
Degree of protection (IP)IP20
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitFront side
Type of control elementPush button
With switched-off indicatorNo
Motor drive integratedNo
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release800 - 8000A
Rated permanent current Iu800A
Overload release current setting320.0 - 800A
With under voltage releaseNo
Motor drive optionalYes
Adjustment range undelayed short-circuit release800 - 8000A
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA061980R1 | T7S 800 PR231/P I IN=800A 3P F F M

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact

0

Degree of protection (IP)

IP20

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Front side

Type of control element

Push button

With switched-off indicator

Motor drive integrated

Number of poles

3

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

800 .. 8000A

Rated permanent current Iu

800A

Overload release current setting

320.0 .. 800A

With under voltage release

Motor drive optional

Adjustment range undelayed short-circuit release

800 .. 8000A

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Device construction

Built-in device fixed built-in technique