Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA061986R1 | T7S 800 PR332/P LSIG In=800A 3p F F M

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
320.0 .. 800A
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Motor drive integrated
Number of auxiliary contacts as change-over contact
0
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Rated voltage
690 .. 690V
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
With under voltage release
DIN rail (top hat rail) mounting optional
Motor drive optional
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
Position of connection for main current circuit
Front side
Number of poles
3
Type of control element
Push button
Complete device with protection unit