Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Motor drive optional
Yes
Type of control element
Push button
Degree of protection (IP)
IP20
Motor drive integrated
No
1SDA062671R1 | T7H 800 PR332/P LSIG In=800A 4p F F M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Position of connection for main current circuit
Front side
Complete device with protection unit
Motor drive optional
Type of control element
Push button
Degree of protection (IP)
IP20
Motor drive integrated