Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Rated voltage
690 - 690V
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
No
Position of connection for main current circuit
Front side
Number of poles
3
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Type of control element
Toggle
Motor drive integrated
No
DIN rail (top hat rail) mounting optional
No
Motor drive optional
No
Complete device with protection unit
Yes
With under voltage release
No
Degree of protection (IP)
IP20
1SDA062678R1 | T7L 800 PR332/P LSI In=800A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Rated voltage
690 .. 690V
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Position of connection for main current circuit
Front side
Number of poles
3
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Type of control element
Toggle
Motor drive integrated
DIN rail (top hat rail) mounting optional
Motor drive optional
Complete device with protection unit
With under voltage release
Degree of protection (IP)
IP20
We use cookies to enhance your experience.