Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA062680R1 | T7L 800 PR332/P LSIRc In=800A 3p F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Type of control element
Toggle
Rated voltage
690 .. 690V
Overload release current setting
320.0 .. 800A
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Integrated earth fault protection
Motor drive optional
Device construction
Built-in device fixed built-in technique
With under voltage release
DIN rail (top hat rail) mounting optional
Complete device with protection unit