Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
320.0 - 800A
With switched-off indicator
No
Device construction
Built-in device fixed built-in technique
Motor drive integrated
No
Type of control element
Push button
Number of auxiliary contacts as change-over contact
0
Number of poles
3
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
Motor drive optional
Yes
1SDA062692R1 | T7L 800 PR331/P LSIG IN=800A 3P F F M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
320.0 .. 800A
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Motor drive integrated
Type of control element
Push button
Number of auxiliary contacts as change-over contact
0
Number of poles
3
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Complete device with protection unit
Motor drive optional