

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Rated voltage
690 - 690V
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
0
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
No
Motor drive integrated
No
Complete device with protection unit
Yes
Type of control element
Push button
Degree of protection (IP)
IP20
Motor drive optional
Yes
Position of connection for main current circuit
Front side
From same serie
1SDA062725R1 | T7V 800 PR332/P LI In=800A 3p F F M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Rated voltage
690 .. 690V
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
0
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
With switched-off indicator
Motor drive integrated
Complete device with protection unit
Type of control element
Push button
Degree of protection (IP)
IP20
Motor drive optional
Position of connection for main current circuit
Front side
From same serie
We use cookies to enhance your experience.