Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
400.0 - 1000A
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Number of poles
4
With switched-off indicator
No
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
No
Motor drive optional
No
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
1SDA062781R1 | T7H 1000 PR332/P LI IN=1000A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
400.0 .. 1000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Number of poles
4
With switched-off indicator
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
Motor drive optional
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20