Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Rated permanent current Iu
1000A
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Overload release current setting
400.0 - 1000A
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
1SDA062863R1 | T7V 1000 PR332/P LSIG In=1000A 4p F F M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Overload release current setting
400.0 .. 1000A
DIN rail (top hat rail) mounting optional
Number of poles
4
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP20
We use cookies to enhance your experience.