Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
1250A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Front side
Type of control element
Toggle
Number of poles
4
Complete device with protection unit
Yes
With under voltage release
No
Motor drive integrated
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Degree of protection (IP)
IP20
Overload release current setting
500.0 - 1250A
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
1875.0 - 15000A
Motor drive optional
No
1SDA062876R1 | T7S 1250 PR331/P LSIG IN=1250A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
1250A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Front side
Type of control element
Toggle
Number of poles
4
Complete device with protection unit
With under voltage release
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Degree of protection (IP)
IP20
Overload release current setting
500.0 .. 1250A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
1875.0 .. 15000A
Motor drive optional