Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Overload release current setting500.0 - 1250A
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitBolt connection
Degree of protection (IP)IP20
With switched-off indicatorNo
Type of control elementToggle
Complete device with protection unitYes
Integrated earth fault protectionNo
Position of connection for main current circuitFront side
With under voltage releaseNo
Adjustment range undelayed short-circuit release1875.0 - 18750A
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Number of poles4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Rated voltage690 - 690V
Motor drive optionalNo
Rated permanent current Iu1250A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA062944R1 | T7L 1250 PR332/P LSIRC IN=1250A 4P

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Overload release current setting

500.0 .. 1250A

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Bolt connection

Degree of protection (IP)

IP20

With switched-off indicator

Type of control element

Toggle

Complete device with protection unit

Integrated earth fault protection

Position of connection for main current circuit

Front side

With under voltage release

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Number of poles

4

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Rated voltage

690 .. 690V

Motor drive optional

Rated permanent current Iu

1250A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.