  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu1600A
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Device constructionBuilt-in device fixed built-in technique
Overload release current setting640.0 - 1600A
Complete device with protection unitYes
Rated voltage690 - 690V
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitBolt connection
Type of control elementToggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Motor drive integratedNo
Number of poles4
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Degree of protection (IP)IP20
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitFront side
Number of auxiliary contacts as normally open contact0
With switched-off indicatorNo
Adjustment range undelayed short-circuit release2400.0 - 24000A
Number of auxiliary contacts as change-over contact0
Motor drive optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA063037R1 | T7H 1600 PR332/P LI IN=1600A 4P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1600A

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Device construction

Built-in device fixed built-in technique

Overload release current setting

640.0 .. 1600A

Complete device with protection unit

Rated voltage

690 .. 690V

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Bolt connection

Type of control element

Toggle

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Motor drive integrated

Number of poles

4

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Degree of protection (IP)

IP20

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Front side

Number of auxiliary contacts as normally open contact

0

With switched-off indicator

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Number of auxiliary contacts as change-over contact

0

Motor drive optional