Aleta.hr
Main Product Image

1SDA063084R1 | T7L 1600 PR331/P LSIG IN=1600A 4P F F M

Code: 1528842

ManufacturerABB
Catalog number1SDA063084R1
Type
EAN code8015644656331

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Overload release current setting640.0 - 1600A
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact0
Degree of protection (IP)IP20
With switched-off indicatorNo
Number of auxiliary contacts as normally open contact0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Motor drive integratedNo
Adjustment range undelayed short-circuit release2400.0 - 19200A
Rated voltage690 - 690V
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
With under voltage releaseNo
Motor drive optionalYes
Rated permanent current Iu1600A
Number of poles4
Position of connection for main current circuitFront side
Integrated earth fault protectionYes
Complete device with protection unitYes
Type of control elementPush button
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA063084R1 | T7L 1600 PR331/P LSIG IN=1600A 4P F F M

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Overload release current setting

640.0 .. 1600A

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

0

Degree of protection (IP)

IP20

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Motor drive integrated

Adjustment range undelayed short-circuit release

2400.0 .. 19200A

Rated voltage

690 .. 690V

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

With under voltage release

Motor drive optional

Rated permanent current Iu

1600A

Number of poles

4

Position of connection for main current circuit

Front side

Integrated earth fault protection

Complete device with protection unit

Type of control element

Push button

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.