Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Overload release current setting
640.0 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Position of connection for main current circuit
Front side
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Number of poles
4
Type of control element
Push button
Motor drive integrated
No
Complete device with protection unit
Yes
1SDA063085R1 | T7L 1600 PR332/P LI IN=1600A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Position of connection for main current circuit
Front side
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Number of poles
4
Type of control element
Push button
Motor drive integrated
Complete device with protection unit