Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA067546R1 | XT2S 160 TMD 6,3-63 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
220 .. 690V
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
4.41 .. 6.3A
Adjustment range undelayed short-circuit release
63.0 .. 63.0A
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Degree of protection (IP)
IP20
With switched-off indicator
Adjustment range short-term delayed short-circuit release
- .. -A
Rated permanent current Iu
6.3A
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Complete device with protection unit