Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA067578R1 | XT2S 160 TMA 80-800 4P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP20
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
400 .. 800A
With switched-off indicator
Adjustment range short-term delayed short-circuit release
- .. -A
Overload release current setting
56.0 .. 80A
Type of electrical connection of main circuit
Bolt connection
With under voltage release
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
80A
Position of connection for main current circuit
Front side
Number of poles
4
Complete device with protection unit
Type of control element
Rocker lever
Motor drive integrated
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
DIN rail (top hat rail) mounting optional