Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA067601R1 | XT2H 160 TMA 80-800 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Rated voltage
220 .. 690V
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Number of auxiliary contacts as change-over contact
0
Adjustment range undelayed short-circuit release
400 .. 800A
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
56.0 .. 80A
With switched-off indicator
Adjustment range short-term delayed short-circuit release
- .. -A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With under voltage release
Motor drive optional
Integrated earth fault protection
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Position of connection for main current circuit
Front side
Rated permanent current Iu
80A
Type of control element
Rocker lever
Device construction
Built-in device fixed built-in technique
Complete device with protection unit