Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Overload release current setting
56.0 - 80A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
400 - 800A
Rated permanent current Iu
160A
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Rated voltage
220 - 690V
Number of poles
4
Integrated earth fault protection
No
Position of connection for main current circuit
Front side
With switched-off indicator
No
Complete device with protection unit
Yes
Type of control element
Toggle
Motor drive optional
Yes
Motor drive integrated
No
With under voltage release
No
Degree of protection (IP)
IP20
1SDA067666R1 | XT2L 160 TMA 80-800 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Overload release current setting
56.0 .. 80A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
400 .. 800A
Rated permanent current Iu
160A
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Rated voltage
220 .. 690V
Number of poles
4
Integrated earth fault protection
Position of connection for main current circuit
Front side
With switched-off indicator
Complete device with protection unit
Type of control element
Toggle
Motor drive optional
Motor drive integrated
With under voltage release
Degree of protection (IP)
IP20
We use cookies to enhance your experience.