Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
160A
Integrated earth fault protection
No
Overload release current setting
1.4 - 2A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
220 - 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
With switched-off indicator
No
With under voltage release
No
Adjustment range undelayed short-circuit release
20 - 20A
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Motor drive integrated
No
Motor drive optional
Yes
Type of control element
Toggle
Number of poles
3
Degree of protection (IP)
IP20
From same serie
1SDA067673R1 | XT2V 160 TMD 2-20 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
160A
Integrated earth fault protection
Overload release current setting
1.4 .. 2A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
220 .. 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
With switched-off indicator
With under voltage release
Adjustment range undelayed short-circuit release
20 .. 20A
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Front side
Motor drive integrated
Motor drive optional
Type of control element
Toggle
Number of poles
3
Degree of protection (IP)
IP20
From same serie