Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Integrated earth fault protection
No
Rated permanent current Iu
160A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
Position of connection for main current circuit
Front side
DIN rail (top hat rail) mounting optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Type of control element
Toggle
Motor drive integrated
No
Motor drive optional
Yes
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
300 - 400A
Overload release current setting
28.0 - 40A
Rated voltage
220 - 690V
With under voltage release
No
Complete device with protection unit
Yes
1SDA067686R1 | XT2V 160 TMA 40-400 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Integrated earth fault protection
Rated permanent current Iu
160A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
Position of connection for main current circuit
Front side
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Type of control element
Toggle
Motor drive integrated
Motor drive optional
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
300 .. 400A
Overload release current setting
28.0 .. 40A
Rated voltage
220 .. 690V
With under voltage release
Complete device with protection unit